NT-40 385 1+1 Type 2 Surge Protective Device

NT-40 385 1+1 type 2 surge protective device from NONTIS. Review full technical specifications, including Type 2 and Class II; enquire about configuration and quantity.

Classification according to EN 61643-11Type 2
Classification according to IEC 61643-11Class II
Maximum continuous operating voltage385V
Maximum continuous operating voltage [N-PE]255V
Nominal discharge current (8/20μs)20kA
Maximum discharge current (8/20μs)40kA
Voltage protection level≤1.8kV

TECHNICAL DATA

Full specifications

Model NT-40 385 1+NPE
Classification according to EN 61643-11 Type 2
Classification according to IEC 61643-11 Class II
Maximum continuous operating voltage Uc 385V
Maximum continuous operating voltage [N-PE] Uc 255V
Nominal discharge current (8/20μs) In 20kA
Maximum discharge current (8/20μs) Imax 40kA
Voltage protection level Up ≤1.8kV
Voltage protection level at 5 kA Up ≤1.4kV
Voltage protection level [N-PE] Up ≤1.5kV
Follow current interrupting rating [ N-PE] Ifi 100Arms
Maximum backup fuse 125A
Response time tA ≤25ns
Response time [N-PE] tA ≤100ns
Operating temperature range Tu -40℃-80℃
Operating status indication Green / red
Minimum conductor cross-section 4mm²
Maximum conductor cross-section 35mm²
Mounting 35 mm standard DIN rail
Housing material Thermoplastic (flammability rating UL94-V0)
Degree of protection IP20

Dimensions & installation

NT-40 385 1+1 dimensional drawing

Dimensions and units are shown as marked in the drawing.

PRODUCT SELECTION

Application

For AC power distribution systems, selected according to the stated SPD classification, operating voltage and configuration.

Specify the required voltage and configuration in your enquiry. Check the ratings for the selected model before installation.

Discuss your NT-40 385 1+1 requirements.