NONTIS · PRODUCT CATALOGUE
NTBD-4L-48 Digital Signal Surge Protector
NTBD-4L-48 digital signal surge protector from NONTIS. Review full technical specifications, including IEC 61643-21 and TYPE2 P1; enquire about configuration and quantity.
Test standardIEC 61643-21
ClassificationTYPE2 P1
Rated operating voltage48V
Maximum continuous operating voltage54VDC / 38.1V AC
Nominal current1A
Total nominal discharge current C2 (8/20μs)20kA
Nominal discharge current per line C2 (8/20μs)10kA
TECHNICAL DATA
Full specifications
| Model | NTBD-4L-48 | |
|---|---|---|
| Test standard | IEC 61643-21 | |
| Classification | TYPE2 P1 | |
| Rated operating voltage | Un | 48V |
| Maximum continuous operating voltage | Uc | 54VDC / 38.1V AC |
| Nominal current | IL | 1A |
| Total nominal discharge current C2 (8/20μs) | In | 20kA |
| Nominal discharge current per line C2 (8/20μs) | In | 10kA |
| Voltage protection level[C2: line-line] | Up | ≤85V |
| Voltage protection level[C2: line-PG] | Up | ≤600V |
| Voltage protection level[ 1kV/ μs C3: line-line] | Up | ≤70V |
| Voltage protection level[ 1kV/ μs C3: line-PG] | Up | ≤550V |
| Series impedance per line | 1 Ohm | |
| Cut-off frequency[line-PG] | fG | 8.7 MHz |
| Capacitance[line-line] | C | ≤0.7 nF |
| Capacitance[line-PG] | C | ≤16 pF |
| Operating temperature range | Tu | -40℃-80℃ |
| Mounting | 35 mm standard DIN rail | |
| Housing material | PA 6.6 | |
| Degree of protection | IP20 |
Dimensions & installation

Dimensions and units are shown as marked in the drawing.
PRODUCT SELECTION
Application
For signal and data lines matching the stated interface, operating voltage and transmission characteristics.
Specify the required voltage and configuration in your enquiry. Check the ratings for the selected model before installation.
Discuss your NTBD-4L-48 requirements.
Send your required configuration, quantity and destination to our team.
sales@nontis.com