Classification according to EN 61643-11Type 2
Classification according to IEC 61643-11Class II
Maximum continuous operating voltage385V
Nominal discharge current (8/20μs)20kA
Maximum discharge current (8/20μs)40kA
Voltage protection level≤1.8kV
Voltage protection level at 5 kA≤1.4kV
TECHNICAL DATA
Full specifications
| Model | NT-40 385 1P | |
|---|---|---|
| Classification according to EN 61643-11 | Type 2 | |
| Classification according to IEC 61643-11 | Class II | |
| Maximum continuous operating voltage | Uc | 385V |
| Nominal discharge current (8/20μs) | In | 20kA |
| Maximum discharge current (8/20μs) | Imax | 40kA |
| Voltage protection level | Up | ≤1.8kV |
| Voltage protection level at 5 kA | Up | ≤1.4kV |
| Maximum backup fuse | 125A | |
| Response time | tA | ≤25ns |
| Operating temperature range | Tu | -40℃-80℃ |
| Operating status indication | Green / red | |
| Minimum conductor cross-section | 4mm² | |
| Maximum conductor cross-section | 35mm² | |
| Mounting | 35 mm standard DIN rail | |
| Housing material | Thermoplastic (flammability rating UL94-V0) | |
| Degree of protection | IP20 |
Dimensions & installation

Dimensions and units are shown as marked in the drawing.
PRODUCT SELECTION
Application
For AC power distribution systems, selected according to the stated SPD classification, operating voltage and configuration.
Specify the required voltage and configuration in your enquiry. Check the ratings for the selected model before installation.
Discuss your NT-40 385 1P requirements.
Send your required configuration, quantity and destination to our team.
sales@nontis.com