NONTIS / Selection guides

How to Choose a Surge Protective Device: Type, Uc and Discharge Capacity

Choose a surge protective device by matching its class, circuit and voltage rating before comparing discharge current. Then check the stated protection level, connection configuration and installation information for the exact model. A large kA value cannot compensate for the wrong AC/DC application, an unsuitable continuous operating voltage or a missing protection path.

This guide follows a practical sequence: classify the duty, describe the electrical system and installation position, match Uc or Ucpv, compare the appropriate discharge ratings, and review Up. The result is a specification brief for a particular circuit. It is not a wiring instruction or a substitute for the project’s electrical design.

Start with the circuit and the required class

Write down what the device will protect: an AC distribution circuit, a PV DC circuit, a low-voltage DC supply, or a signal connection. These are different selection tasks. A voltage number alone does not describe the application, and a power SPD is not an interchangeable substitute for a signal-line protector.

Next record the class required by the protection design. The AC product tables distinguish Type 1 / Class I, Type 1+2 / Class I+II, Type 2 / Class II and Type 3 / Class III. Preserve both labels when preparing a comparison. They describe the classifications reported in the tables; they are not evidence of a third-party certification.

For an initial shortlist, use the class as a filter rather than trying to infer it from a model name. A product described as combined Type 1+2 must have that classification in its own table. The presence of a large maximum discharge current does not, by itself, turn a Type 2 entry into Type 1.

Selection step Information to collect What it prevents
Circuit AC, PV DC, low-voltage DC or signal Comparing devices from different application families
Class Required Type and corresponding Class entry Choosing only by the largest current number
System and position Circuit diagram, supply arrangement and intended panel position Treating a generic product description as a project design
Continuous voltage Relevant Uc or Ucpv, including protection path Confusing normal operation with impulse performance
Discharge duty Iimp, In and Imax where stated Mixing different tests or inventing missing values
Protection level Up with its path and test condition Comparing unlike limits as if they were identical

Describe the system and installation position

Record the supply arrangement, the conductors to be protected and the intended installation point. Include a circuit drawing if available. Configuration names such as 1P, 2P, 3P, 4P and 3+1 should be read alongside the connection information, not treated as a complete description of system suitability.

The reviewed three-phase tables demonstrate why the individual paths matter. The NT-25GR 3+1 table separates L-N and N-PE voltage values. Its N-PE impulse-current entry is also different from the other listed impulse-current entry. Copying one headline number into every path would change the specification.

An enquiry should therefore state which board or circuit is involved and whether the project has already defined the SPD class and arrangement. If that information is undecided, describe the uncertainty explicitly. The product tables do not establish a universal rule that every incoming board uses the same model or that every downstream board uses an identical configuration.

For the distinction between class evidence and position in a distribution system, see our guide to Type 1 vs Type 2 SPDs.

Match Uc or Ucpv to the actual application

Uc is the maximum continuous operating voltage reported for the device. PV tables use Ucpv for the corresponding PV rating. These values are different from a discharge-current rating and from the voltage protection level. Keep the symbols attached to the numbers throughout the selection process.

The NT-25GR 3+1 table includes 150 V, 275 V and 385 V variants for the L-N rating, while the N-PE entry is 255 V. The NT-12.5M 320 3+NPE table lists Uc 320 V and a separate N-PE Uc of 255 V. Those entries illustrate model and path distinctions, not a universal recommendation for any nominal supply voltage.

DC selection needs the same discipline. The NT-40 48 table lists nominal operating voltage Un 48 VDC and maximum continuous operating voltage Uc 65 VDC. The two labels have different meanings; a buyer should not rewrite the model’s continuous rating as 48 V simply because that number appears in its name.

For PV, the reviewed NTPV3-1000 table states Ucpv 1000 V DC, while NTPV2-600 states Ucpv 600 V. Do not substitute a nominal AC voltage or a different family’s value. Establish the project’s required continuous-voltage rating and compare the relevant entry for the exact proposed device.

Compare discharge ratings with their waveforms

Iimp, In and Imax are separate fields. The reviewed AC Type 1 and combined tables identify Iimp with a 10/350 μs waveform. In and Imax entries use 8/20 μs where specified. Retain those waveform labels in your comparison sheet.

The NT-25GR 3+1 table lists Iimp 25 kA and a separate N-PE Iimp of 100 kA. The NT-12.5M 320 3+NPE table lists Iimp 12.5 kA, In 20 kA and Imax 65 kA, with separate N-PE values. The NT-40 385 3+NPE table lists In 20 kA and Imax 40 kA. None of those numbers should be silently converted into another current field.

Example Table classification Selected discharge entries
NT-25GR 3+1 Type 1 / Class I Iimp 25 kA; separate N-PE Iimp 100 kA
NT-12.5M 320 3+NPE Type 1+2 / Class I+II Iimp 12.5 kA; In 20 kA; Imax 65 kA
NT-40 385 3+NPE Type 2 / Class II In 20 kA; Imax 40 kA
NT-20DP 2P Type 3 / Class III In 10 kA; Imax 20 kA; Uoc 10 kV

The table is a reading aid, not a ranking. The values do not establish that one device can replace another, nor do they establish a number of lightning events or an expected service life. Where a rating is absent, leave it absent and request the relevant information.

Review Up without losing its conditions

Up is the stated voltage protection level. Compare it only after the application, voltage and test context are clear. The lowest number in a mixed list is not automatically the best device for a circuit.

The NT-40 385 3+NPE table gives Up ≤1.8 kV and a separate value of ≤1.4 kV at 5 kA. Those are distinct entries. Publishing only the smaller figure without its test current would conceal a material condition. The same table lists N-PE Up separately at ≤1.5 kV.

PV examples also need their own context. NTPV3-1000 lists Up ≤4.0 kV; NTPV2-600 lists Up ≤2.2 kV. These belong to different continuous-voltage and class specifications. Compare the complete proposed device against the equipment requirements rather than selecting from an isolated Up column.

For signal circuits, protection paths and transmission requirements add further checks. Use the separate signal surge protector selection guide instead of carrying power-SPD assumptions across to an interface.

Check installation data and supporting protection

After the electrical shortlist, review the exact device’s mounting, terminal sizes, enclosure protection and supporting protective-device information. The source tables contain maximum backup-fuse entries for some power devices. These are model-specific limits; they are not permission to install that fuse value in every circuit.

Do not fill a missing terminal size, fuse value or mounting dimension from a visually similar device. Record the gap, identify the proposed model and ask for its installation information. Likewise, a picture of a DIN-rail device does not provide the dimensions or wiring details needed for a panel drawing.

The project’s available fault conditions, conductor arrangement and installation requirements still need to be checked against the applicable device documentation. This guide intentionally does not prescribe conductor lengths, torque settings, fuse coordination or installation locations unsupported by the reviewed data.

Turn the shortlist into a useful enquiry

A useful request names the application, voltage, required class, configuration and quantity. Add the installation drawing and any equipment protection-level requirement. If you already have an NT model in mind, include the complete suffix and voltage variant rather than only the family name.

Keep a separate list of open questions. For example: confirm the N-PE rating, provide the installation drawing, clarify the backup protection requirement, or supply the applicable model documentation. This makes an unanswered field visible instead of disguising it as an assumption.

Send the brief to NONTIS with your destination market and intended order quantity. Our product range overview groups the AC, DC/PV, signal, LED and backup-protection families so you can direct the enquiry to the relevant application without treating all surge devices as equivalent.